MGE Galaxy 3500 40kVA 400V, Start-Up 5X8 – G35T40KHS
Overview
Galaxy 3500Features & Benefits
Total Cost of Ownership
-
Temperature-compensated battery chargingProlongs battery life by regulating the charge voltage according to battery temperature.
-
Excellent footprintSmall UPS footprint provides maximum usage of valuable electrical room floorspace
-
Input power factor correctionMinimizes installation costs by enabling the use of smaller generators and cabling.
Sustainability
-
EU CoC for UPSEnsures that UPSs sold in the EU are highly efficient
Serviceability
-
Front-access servicingSimplifies installation and UPS maintenance while minimizing space requirements.
-
User-replaceable air filtersEnables quick and simple replacement of air filters.
-
Multiple levels of serviceWith the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like APC to do for you.
-
Battery replacement without toolsEnables fast battery replacement, lowering Mean Time to Repair (MTTR).
-
7×24 telephone technical supportOur experienced technical support engineers are available to answer your questions, giving you peace of mind knowing the help you need is there when you need it.
Manageability
-
LCD graphics displayText and mimic diagrams that display modes of operation, system parameters and alarms.
-
Environmental monitoringPrevent equipment failure from a full range of threatening environmental conditions.
-
Built-in Web/SNMP managementFull-featured management via a Web browser as well as comprehensive management from a Network Management System.
-
Audible alarmsProvides notification of changing utility power and UPS power conditions
Availability
-
Dual mains inputIncreases availability by allowing the UPS to be connected to two separate power sources.
-
Automatic internal bypassSupplies utility power to the connected loads in the event of a UPS power overload or fault.
-
Generator compatibleEnsures clean, uninterrupted power to protected equipment when generator power is used.
-
Advanced electrical featuresExcellent power conditioning, very low harmonic distortion through IGBT rectifier, input power factor correction, and high power efficiency
-
Frequency and voltage regulationGives higher application availability by correcting poor frequency and voltage conditions without using the battery.
-
Hot-swappable batteriesEnsures clean, uninterrupted power to protected equipment while batteries are being replaced
-
Parallel-capacity capableIncreases total power capacity by using multiple uninterruptible power supplies simultaneously.
Detailed Tech Specification
Output
-
Output power capacity
32.0 KWatts / 40.0 kVA
-
Max Configurable Power (Watts)
32.0 KWatts / 40.0 kVA
-
Nominal Output Voltage
400V 3PH
-
Output Voltage Note
Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
-
Efficiency at Full Load
95.8 %
-
Output Voltage Distortion
Less than 5%
-
Output Frequency (sync to mains)
47 – 53 Hz for 50 Hz nominal
-
Output Frequency (not synced)
50Hz +/- 0.1% for 50Hz nominal
-
Other Output Voltages
380, 415
-
Load Crest Factor
Unlimited
-
Topology
Double Conversion Online
-
Waveform type
Sine wave
-
Overload Operation
10 minutes @ 125% and 60 seconds @ 150%
-
Output Voltage THD
< 2% for 0 to 100% linear load and < 5% for full non linear load
-
Output Voltage Tolerance
+/-1% static and +/- 5% at 100% load step
-
Bypass
Built-in Maintenance Bypass, Built-in Static Bypass
Input
-
Nominal Input Voltage
400V 3PH
-
Input frequency
40 – 70 Hz (auto sensing)
-
Input Connections
Hard Wire 5-wire (3PH + N + G)
-
Input voltage range for main operations
304 – 477V
-
Input voltage adjustable range for mains operation
340 – 460 (400V)V
-
Efficiency at Full Load
95.8 %
-
Input Total Harmonic Distortion
Less than 5% for full load
-
Type of Input Protection Required
3-pole breaker
-
Other Input Voltages
380, 415
-
Maximum Input Current
54.0A
-
Input Power Factor at Full Load
0.98
Batteries & Runtime
-
Battery type
No internal battery supplied with UPS – can be used with external third party batteries or SYBTH4
-
Nominal Battery Voltage
+/-192 V (split battery referenced to neutral)
-
End of Discharge Battery Voltage
+/-154 V
-
Overload Operation
10 minutes @ 125% and 60 seconds @ 150%
Communications & Management
-
Interface Port(s)
DB-9 RS-232 , G35T
-
Pre-Installed SmartSlot™ Cards
-
Control panel
Multi-function LCD status and control console
-
Audible Alarm
Alarm when on battery : distinctive low battery alarm : configurable delays
-
Emergency Power Off (EPO)
Yes
Physical
-
Maximum Height
1491mm , 149.1CM
-
Maximum Width
523mm , 52.3CM
-
Maximum Depth
838mm , 83.8CM
-
Net Weight
294.0KG
-
Shipping weight
325.0KG
-
Shipping Height
1643mm , 164.3CM
-
Shipping Width
650mm , 65.0CM
-
Shipping Depth
1062mm , 106.2CM
Environmental
-
Operating Temperature
0 – 40 °C
-
Operating Relative Humidity
0 – 95 %
-
Operating Elevation
0-999.9meters
-
Storage Temperature
-15 – 45 °C
-
Storage Relative Humidity
0 – 95 %
-
Storage Elevation
0-15000meters
-
Audible noise at 1 meter from surface of unit
55.0dBA
-
Online thermal dissipation
5132.0BTU/hr
-
Protection Class
IP 51
Reviews
There are no reviews yet.