Galaxy VS UPS 10kW 400V, 1 internal 9Ah smart modular battery string, expandable to 4, Start-up 5×8 – GVSUPS10KB4HS
- Max Configurable Power (Watts) : 10.0kWatts / 10.0kVA
- Other Input/Output Voltages : 380 V, 415 V
- Waveform type : Sine wave
- Bypass : Built-in static bypass
- Battery type : Internal modular battery, VRLA
- Warranty : 1 Year
PN : GVSUPS10KB4HS
Galaxy VS UPS 10kW 400V, 1 internal 9Ah smart modular battery string, expandable to 4, Start-up 5×8
Overview
Galaxy VS Features & Benefits
Total cost of Ownership
Robust operation
No power derating in kW up to 40°C or 104°F.
Wide input voltage range
Designed for harsh electrical environments to save battery life.
High efficiency in double conversion mode
Consistently high power quality at high efficiency, even at low load levels. Any disturbances on the distribution waveform are regenerated via the zero transfer time AC to DC then DC to AC conversion process. The battery is only used as a back-up source.
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Compatible with Galaxy Lithium-ion Battery Cabinets
Reduces system footprint and weight, cooling and maintenance requirements, and total cost of ownership; offers double the life of VRLA batteries; and improves backup storage predictability and manageability. Galaxy VS UPSs for external batteries are compatible with Galaxy Lithium-ion Battery Cabinets.
ECOnversion mode
Operating mode that ensures ultra high efficiency while charging the batteries, conditioning the load power factor and ensuring a Class 1 output voltage regulation.
Compact UPS
High-density technology and full front access make this UPS a footprint saver well suited for confined spaces.
Serviceability
Modular UPS design
Provides design redundancy and fast serviceability with improved mean time to repair, via self-diagnosing, field-replaceable modules.
Multiple levels of service offers
With the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like Schneider Electric to do for you.
EcoStruxure IT Expert
From your smartphone or computer, connect to our cloud-based, do-it-yourself monitoring system that collects, organizes, and distributes critical alerts and key information in real time, providing a unified view of even highly distributed physical infrastructure environments. Optimize your uptime and maintenance planning, and anticipate infrastructure issues before they occur with advanced analytics and performance benchmarking. Available in select countries. To learn more, visit a target=”_blank” href=”http://www.ecostruxureit.com”ecostruxureit.com/a.
Front-access servicing
Simplifies installation and UPS maintenance while minimizing space requirements.
Availability
Embedded Network Management Card
Allows you to remotely manage alert thresholds and monitor your UPS over EcoStruxure IT, Web, SNMP, or Modbus TCP and Modbus RTU.
Flexible DC bus
Optimizes battery sizing and supports a wide range of energy storage technologies, including VRLA, Li-ion, and NiCd batteries.
Built-in backfeed protection
Full built-in backfeed contactor ensures that no electricity is sent back to the grid.
Parallel-capacity capability
Increases total power capacity by using multiple uninterruptible power supplies simultaneously.
Parallel-redundant capability
Powers the connected equipment with multiple uninterruptible power supplies and redundant fan design to increase system redundancy.
Published on lastbestdeal.com
Detailed Tech Specification
Output
Max Configurable Power (Watts)
- 10.0kWatts / 10.0kVA
Output Voltage Distortion
- Less than 3 %
Output Frequency (sync to mains)
- 50 Hz +/- 0.1 % For 50 Hz nominal Unsynchronised, 50 Hz Sync to mains, 60 Hz +/- 0.1 % For 60 Hz nominal Unsynchronised, 60 Hz Sync to mains
Other Output Voltages
- 380 V, 415 V
Load Crest Factor
- 2.5
Waveform type
- Sine wave
Overload Operation
- 10 minutes at 125% and 60 seconds at 150%
Output Voltage THD
- < 1% linear load and < 3% non-linear load
Output Voltage Tolerance
- +/-1% after 50ms
Bypass
- Built-in static bypass
Input
Input frequency
- 40 – 70 Hz
Input voltage range for main operations
- 340 – 460 (400 V)V
Input Total Harmonic Distortion
- Less than 3 % for full load
Other Input Voltages
- 380 V, 415 V
Maximum Short Circuit Withstand (Icw)
- 65.0kAmps
Input Power Factor at Full Load
- 0.99
Batteries & Runtime
Battery type
- Internal modular battery, VRLA
Nominal Battery Voltage
- 480 V
End of Discharge Maximum Battery Current
- 27.0A
End of Discharge Battery Voltage
- 384 V DC
Efficiency
Communications & Management
Interface Port(s)
- GVS_Parallel, GVS_WideUPS_AirFilter, GVS_WideUPSMBC_SeismicKit
Control panel
- Touch screen LCD user interface
Audible Alarm
- Audible and visible alarms prioritized by severity
Available SmartSlot™ Interface Quantity
- 1
Physical
Maximum Height
- 1485MM, 148.5CM
Maximum Width
- 521MM, 52.1CM
Maximum Depth
- 847MM, 84.7CM
Net Weight
- 320.0KG
Shipping weight
- 360.0KG
Shipping Height
- 1680MM, 168.0CM
Shipping Width
- 640MM, 64.0CM
Shipping Depth
- 990MM, 99.0CM
Color
- White
Environmental
Operating Temperature
- 0 – 40 °C
Operating Relative Humidity
- 0 – 95 (Non-condensing) %
Operating Elevation
- 0 – 1000.05meters
Storage Temperature
- -15 – 40 °C
Storage Relative Humidity
- 0 – 95 (Non-condensing) %
Storage Elevation
- 0 – 3048meters
Audible noise at 1 meter from surface of unit
- 55.0dBA
Conformance
Approvals
- CSA C22.2 No 107.3, EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, IEC 60721-4-2 level 2M2, UL 1778 5th edition
Standard warranty
- 1 year repair or replace
Sustainable Offer Status
RoHS
- Compliant
PEP
- Available in Documentation tab
Reviews