Galaxy VS UPS 10kW 400V, 1 internal 7Ah smart modular battery string, expandable to 2, Start-up 5×8 – GVSUPS10KB2HS
- Max Configurable Power (Watts) : 10.0kWatts / 10.0kVA
- Other Input/Output Voltages : 380 V, 415 V
- Waveform type : Sine wave
- Bypass : Built-in static bypass
- Battery type : Internal modular battery, VRLA
- Warranty : 1 Year
PN : GVSUPS10KB2HS
Galaxy VS UPS 10kW 400V, 1 internal 7Ah smart modular battery string, expandable to 2, Start-up 5×8
Overview
Galaxy VS Features & Benefits
Availability
Embedded Network Management Card
Allows you to remotely manage alert thresholds and monitor your UPS over EcoStruxure IT, Web, SNMP, or Modbus TCP and Modbus RTU.
Flexible DC bus
Optimizes battery sizing and supports a wide range of energy storage technologies, including VRLA, Li-ion, and NiCd batteries.
Parallel-capacity capability
Increases total power capacity by using multiple uninterruptible power supplies simultaneously.
Built-in backfeed protection
Full built-in backfeed contactor ensures that no electricity is sent back to the grid.
Parallel-redundant capability
Powers the connected equipment with multiple uninterruptible power supplies and redundant fan design to increase system redundancy.
Serviceability
Front-access servicing
Simplifies installation and UPS maintenance while minimizing space requirements.
Modular UPS design
Provides design redundancy and fast serviceability with improved mean time to repair, via self-diagnosing, field-replaceable modules.
Multiple levels of service offers
With the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like Schneider Electric to do for you.
EcoStruxure IT Expert
From your smartphone or computer, connect to our cloud-based, do-it-yourself monitoring system that collects, organizes, and distributes critical alerts and key information in real time, providing a unified view of even highly distributed physical infrastructure environments. Optimize your uptime and maintenance planning, and anticipate infrastructure issues before they occur with advanced analytics and performance benchmarking. Available in select countries. To learn more, visit a target=”_blank” href=”http://www.ecostruxureit.com”ecostruxureit.com/a.
Total cost of Ownership
ECOnversion mode
Operating mode that ensures ultra high efficiency while charging the batteries, conditioning the load power factor and ensuring a Class 1 output voltage regulation.
High efficiency in double conversion mode
Consistently high power quality at high efficiency, even at low load levels. Any disturbances on the distribution waveform are regenerated via the zero transfer time AC to DC then DC to AC conversion process. The battery is only used as a back-up source.
Compatible with Galaxy Lithium-ion Battery Cabinets
Reduces system footprint and weight, cooling and maintenance requirements, and total cost of ownership; offers double the life of VRLA batteries; and improves backup storage predictability and manageability. Galaxy VS UPSs for external batteries are compatible with Galaxy Lithium-ion Battery Cabinets.
Compact UPS
High-density technology and full front access make this UPS a footprint saver well suited for confined spaces.
Input power factor correction
Minimizes installation costs by enabling the use of smaller generators and cabling.
Robust operation
No power derating in kW up to 40°C or 104°F.
Wide input voltage range
Designed for harsh electrical environments to save battery life.
Published on lastbestdeal.com
Detailed Tech Specification
Output
- 10.0kWatts / 10.0kVA
- Less than 3 %
- 50 Hz +/- 0.1 %
- For 50 Hz nominal Unsynchronised, 50 Hz Sync to mains,
- 60 Hz +/- 0.1 %
- For 60 Hz nominal Unsynchronised, 60 Hz Sync to mains
- 380 V, 415 V
- 2.5
- Sine wave
- 10 minutes at 125% and 60 seconds at 150%
- < 1% linear load and < 3% non-linear load
- +/-1% after 50ms
- Built-in static bypass
Input
- 40 – 70 Hz
- 340 – 460 (400 V)V
- Less than 3 % for full load
- 380 V, 415 V
- 65.0kAmps
Batteries & Runtime
- Internal modular battery, VRLA
- 480 V
- 27.0A
- 384 V DC
Communications & Management
- GVS_350mm_AirFilter, GVS_350mm_Seismic, GVS_Parallel
- Touch screen LCD user interface
- Audible and visible alarms prioritized by severity
- 1
Physical
- 1485MM, 148.5CM
- 333MM, 33.3CM
- 847MM, 84.7CM
- 245.0KG
- 270.0KG
- 1690MM, 169.0CM
- 640MM, 64.0CM
- 990MM, 99.0CM
- White
Environmental
- 0 – 40 °C
- 0 – 95 (Non-condensing) %
- 0 – 1000.05meters
- -15 – 40 °C
- 10 – 80 (Non-condensing) %
- 0 – 3048meters
- 5.0dBA
- 1240.0BTU/hr
- IP20
Conformance
- CSA C22.2 No 107.3, EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, FCC part 15 class A, IEC 60721-4-2 level 2M2, UL 1778 5th edition
- 1 year on-site repair or replace with factory authorized Start-Up Sustainable Offer Status
- Compliant
- Available in Documentation tab