Vertiv GXTRT+1ph UPS 2kVA 230V – GXTRT-2000IRT2UXL
GXTRT-2000IRT2UXL
The high output power factor (0.9) of the single-phase Liebert® GXT RT+ uninterruptible power supply (UPS) provides high performance protection for connected devices from a wide range of input voltages. With rack or tower mounting flexibility and an ECO mode of operation, the energy efficient unit delivers maximum value. Its compatibility with external battery cabinets and multiple monitoring options makes the compact UPS ideal for deployments in space-constrained or edge facilities.
Overview
Featuring online technology with two stages of power conversion, the Liebert® GXT RT+ UPS has a 0.9 output power factor that is higher than the majority of comparable competitor models. Input voltages for connected devices can range from 120-300V AC. The flexible rack/tower form factor features a user-friendly liquid crystal display (LCD) that provides UPS status and configuration information at a glance. The unit’s smart battery charger design, ECO operation mode enables up to 95% efficiency for a compelling total cost of ownership (TCO). Additionally, the UPS serial connections enable remote access to power consumption monitoring options.
Key Benefits
- Installation flexibility, high output power factor, and energy efficient operation make this an affordable UPS solution for high performance protection.
- Multiple monitoring options and compact design make the UPS ideal for space-constrained or edge of network deployments.
- High efficiency up to 95% helps to achieve energy savings and a lower TCO
Features
- Online double conversion technology
- High output power factor of 0.9
- Compact and flexible design with rack or tower mounting options
- High efficiency ECO mode of operation
- User-friendly LCD
- Smart battery charger design
- Wide input voltage operation
Benefits
- Essential protection UPS with high performance
- Flexible and ready for growth
- More usable power supporting more connected loads for space and cost savings
- Simplified UPS selection and deployment
- Energy savings and lower TCO
- Easy installation and configuration with at-a-glance UPS status
- Improved availability during main power fluctuations
Short Tech Specification
Vertiv GXT RT+ 1ph UPS, 2kVA, input plug IEC60320 C14, 2U, output – 230V, output socket groups (6)C13 |
Detailed Tech Specification
GXTRT-2000IRT2UXL
Rating
Power Rating
- 2000 VA / 1800 W
Dimensions (D×W×H)
Unit
-
470 x 430 x 85
Weight (kg)
Unit
- 21
Input AC
Input Voltage
- 230 VAC
Frequency
- 40Hz ~ 70Hz; Auto Sensing
Input Power Cord
-
C14
Output AC
Output Voltage
- 200/208/220/230/240 VAC
Output Receptacles
-
C13×8
Waveform
-
Sine wave
Utility(AC) Model Overload
-
>200% for 250ms; 150- 200% for 2 seconds; 125- 150% for 50 seconds; 105-125% 60 seconds;
Internal Charger
Charging current
- Nominal 2.2 A; Maximum 8 A
Battery
Type
- Valve-regulated, non-spillable, lead acid
Qty×V×Rating
- 4 × 12V × 9.0Ah
Recharge Time
- 4 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries
Only)
Environmental Requirements
Operating Temperature,°F (°C)
- +32 to +122 (0 to 50); Operating temperature may be increased to 122°F (50°C with a 10% de-rating of
the output power
Storage Temperature, °F(°C)
- –4to +140 (-20 to 60)( contain batteries will be from –15 to 40°C.)
Relative Humidity
- 0% to 95%, non-condensing
Operating Elevation
- Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating
Audible Noise
- <48dBA max @ 3ft. (1m) front and sides <48dBA max @ 3ft. (1m) rear
Agency
Safety
- EN 62040-1:2008+A1:2013;
GS mark;
UL 1778 5th Edition and CSA 22.2 No. 107.1
EMC
- EN 62040-2:2006
EN 61000-3-2:2014
EN 61000-3-3:2013
Transportation
- ISTA Procedure 1A
Surge Immunity
- ANSI C62.41 Category B IEC 61000-4-5 Surges/Lightning
RFI/EMI
- CISPR22 Class A